Toshiba G9000 SERIES Installation And Operation Manual page 25

480/480 v 1000kva
Hide thumbs Also See for G9000 SERIES:
Table of Contents

Advertisement

Configuration
Voltage
Frequency
Bypass Overload
Type
Ride Through
Nominal Voltage
Minimum Voltage
Float Voltage
Number of Cells
Max DC Ripple Current while
Charging
DC Ripple Current (% of Full
Load Current)
Max DC Charge Current
Max. Discharge Current
Batt. Capacity Required at
Full Load Output
Configuration
Voltage
Voltage Regulation
Voltage Unbalance
Voltage THD (V
)
OUT
Voltage Adjustment
Crest Factor
Transient Response
Transient Recovery
Output Current
Frequency
Frequency Synch. Range
Frequency Slew Rate
Frequency Regulation
Phase Displacement
Power Factor
Power Factor Range
Inverter Overload
System Overload
(with bypass available)
MTBF
w/ Bypass
w/o Bypass
Withstand Rating
Cooling
Operating Temperature
G9000 1000kVA Installation and Operation Manual – 91469-004
G9000 1000 kVA SPECIFICATIONS
STATIC BYPASS INPUT
480 V
BATTERY
Application Specific
AC OUTPUT
2% maximum at 100% unbalanced load
2% maximum THD at 100% Linear Load
5% maximum THD at 100% Non-linear Load
±3% (User selectable)
+/-2% maximum at 100% load step
+/-1% maximum at loss/return of AC power
+/-5% maximum at load transfer to/from static bypass
±1% to ± 5% (selectable in 1% increments)
1 Hz/s to 5 Hz/s (selectable in 1 Hz/s increments)
+/-0.01% in free running mode
1deg. maximum at 100% load
0.7 lagging to 0.8 leading
125% for 10 minutes
150% for 60 seconds
100,000 AIC with Optional Fuses
ENVIRONMENTAL
32゚F to 104゚F ( 0゚C to 40゚C).
Recommended : 68゚F to 86゚F ( 20゚C to 30゚C)
3 phase, 3 wire
+/-10%
60 Hz +/-5%
500% for 1 cycle
Lead Acid
480 Vdc
400 Vdc
Up to 545 Vdc
240
42 A
1.9%
200 A
2586 A
1036 kW
3 phase, 3 wire
480 V
+/-1%
2.3
Less than 20ms
1203 A
60 Hz
1.0 (unity)
500% for 1 cycle
2,600,000 hrs.
100,000 hrs.
Forced Air
15