Toshiba G9000 SERIES Installation And Operation Manual page 63

480/480 v 1000kva
Hide thumbs Also See for G9000 SERIES:
Table of Contents

Advertisement

Code
indication
(Note 2)
MA810
INVERTER OVERLOAD
MA817
EMERG.STOP ACTIV.
MA824
CB2 OPEN
MA834
BATTERY DEPLETED
MA836
INVERTER OVERLOAD
MA870
BALANCER OVERLOAD
MF001
I/P CIRCUIT ABL.
MF002
CONV OVERCURRENT
MF003
CONVERTER ABNL.
MF102
DC OVERVOLTAGE
MF103
DC UNDERVOLTAGE
MF104
DISCHARGE FAULT
MF108
CHOP OVERCURRENT
MF109
DC UNBALANCED
MF110
ZERO PHASE OC.
MF111
CTRL.CIRCUIT ERR.
MF112
DC CIRCUIT ABNL.
MF119
DC GROUND FAULT
MF128
CTRL.PWR. ABNL.
MF154
CB2 ABNORMAL
MF159
DC GROUND FAULT
MF160
CTRL.CIRCUIT ERR.
MF162
BATTERY ABNORMAL
MF163
BAT.VOLTAGE ABNL.
MF179
DC GROUND FAULT
MF201
INVERTER OV.
MF202
IINVERTER UV.
MF203
INVERTER OC.
MF204
O/P CIRCUIT ABNL.
MF207
ZERO PHASE OC.
MF208
CTRL.CIRCUIT ERR.
MF210
52C ABNORMAL
MF213
OVERTEMPERATURE
MF214
COOLING FAN ABNL.
MF217
INVERTER OV.
MF230
ZERO PHASE OC.
G9000 Installation and Operation Manual – 61480-012
UPS MODULE FAULTS CODE LIST
Status
message
Short time over-current has exceeded 150% of the
rated current
The emergency stop was activated by the EPO switch
or an external contact.
The battery disconnect contactor CB2 open.
The battery voltage has reached the depleted level.
The output load active power has exceeded 110% of
the rated current.
The UPS detected a neutral point voltage unbalance.
Detection of a large variation of the reference error
signal.
Detection of converter overcurrent.
Pre-charging circuit is not working properly.
DC voltage surpasses the overvoltage level.
DC voltage dropped below the undervoltage level.
Capacitor voltage is higher than 100V at 5 minutes
after module stop.
Detection of DC overcurrent.
Major unbalance of the neutral point voltage.
Major unbalance of the neutral point voltage.
Battery current unbalance.
Sudden change of the DC voltage level.
Detection of DC ground fault.
Power supply voltage to IGBT driver PCB is below the
specified level.
During UVT, status signal from CB2 is ON.
Detection of DC ground fault.
Abnormal behavior of DC current sensor.
Failure detection based on battery self-check.
Battery voltage is abnormal.
Detection of DC ground fault continued for 5 minutes.
Detection of output overvoltage.
Output voltage dropped.
Detection of inverter overcurrent.
Detection of a large variation of the reference error
signal (current reference and actual current).
Inverter zero-sequence overcurrent.
Cross current is abnormal.
Error to open the contactor 52C.
Heatsink temperature exceeds thermal settings.
Thermal relay activated protection.
Detection of inverter output phase overvoltage.
Detection of zero-sequence overcurrent.
Meaning
External relay
contact
(Note 1)
Alarm
Overload
Alarm
Alarm
Major
End-of-
Discharge
Alarm
Overload
Alarm
Overload
Major
Major
Major
Major
Major
Minor
Major
Major
Major
Major
Major
Major
Major
Minor
Minor
Minor
Minor
Minor
Minor
Major
Major
Major
Major
Major
Major
Major
Major
Major
Major
Major
53