APPENDIX A – Installation Planning Guide (IPG)
Installation Planning Guide for 1000kVA UPS
Dimensions
(W x D x H)
Inches
118.2" x 35.5" x 80.7"*
* Height includes removable an housing – Frame height is 78.7."
** 0" clearance for peripheral equipment, 1" clearance for walls.
Maximum Input Power Demand
Normal Mode (Recharge Mode)
kVA
PF
1043 (1127)
> 0.99
Alternate (Bypass) AC Input (480V 3-Phase / 3-Wire)
Maximum Input Power Demand
kVA
PF
Amps (Max.)
1000
1.0
1203
Battery Capacity Required
Maximum Discharge
for Full Load Output
kWB
1036 @ 1.0 PF
Rated Output Power
kVA
PF
Amps
1000
1.0
1203
Important Notes:
1.
Maximum input current is limited to 108% of the full-load
input current.
2.
Output load conductors are to be installed in separate
conduit from input conductors.
3.
Control wires and power wires are to be installed in
separate conduits.
4.
Recommended AC input and output overcurrent protection
based on continuous full load current per NEC.
5.
Wiring shall comply with all applicable national and local
electrical codes.
6.
Grounding conductors to be sized per NEC Article 250-122.
Neutral conductors to be sized per NEC Article 310.15.
- Primary AC Input: 3φ, 3-wire + ground.
- Alternate AC Input: 3φ, 3-wire + ground.
- AC Output: 3φ, 3-wire + ground.
- DC Input: 2-wire (Positive/Negative) + ground.
7.
Nominal battery voltage based on the use of VRLA type
batteries (2.0 volts/cell nominal).
8.
Maximum battery discharge current based on lowest
permissible discharge voltage of 1.67 VPC.
9.
DC wires should be sized to allow not more than a 2-volt
drop at maximum discharge current.
10. Weights do not include batteries or other auxiliary
equipment external to the UPS.
G9000 Installation and Operation Manual – 61480-012
Standard System: 480V Input, 480V Output
General Mechanical Information
Floor
Approximate Full-Load
Weight
Loading
Heat Rejection
2
Lbs.
Lbs./ft.
kBtu/Hr
6613
227
Primary AC Input (480V 3-Phase / 3-Wire)
Suggested External
Overcurrent Protection
Amps
1255 (1356)
1600 AT
Suggested External
Overcurrent Protection
Amps
1600 AT
Battery Input (480VDC Nominal)
Suggested External
at Full Load Output
Overcurrent Protection
Amps DC
Amps
2586
3000 AT
AC Output (480V 3-Phase / 3-Wire)
Suggested External
Overcurrent Protection
Amps
1600 AT
Mechanical Clearance (Inches)from UPS for
Ventilation and Maintenance Access
Top
Front
112.8
24"
39"
External Feeder Wire Size: Min. – Max. Per Phase
Amps
AWG or kcmil at 75º C Temp. Rating
(5) 400 kcmil – (6) 300 kcmil
External Feeder Wire Size:
Min. – Max. Per Phase
AWG or kcmil at 75º C Temp. Rating
(5) 400 kcmil – (6) 300 kcmil
External Feeder Wire Size: Min. – Max.
AWG or kcmil at 75º C Temp. Rating
(8) 500 kcmil – (10) 350 kcmil
External Feeder Wire Size:
Min. – Max. Per Phase
AWG or kcmil at 75º C Temp. Rating
(5) 400 kcmil – (6) 300 kcmil
11. Cable sizing calculations based on the following assumptions:
- Minimum size is smallest size based on ampacity at 30 °C.
- Maximum size cable is based on cable bend radius
limitations at the UPS terminals.
- Not more than 3 current-carrying conductors installed in
conduit in ambient temperature of 30 °C.
- Temperature rating of copper conductors/terminals: 75 °C in
conduit.
- Reference: 2005 NEC Handbook, Table 310.16.
NOTE: Consult latest edition of applicable
national and local codes for possible
variations.
12. Ratings of wires and overcurrent devices are suggested
minimums. Consult with a registered Professional Engineer
within your local area for proper size selections.