Omron NV Series Programming Manual page 195

Programmable
Hide thumbs Also See for NV Series:
Table of Contents

Advertisement

Recipes
Words for Controlling
Recipes
Bit
15
Word
n
n+1
n+2
n+3
174
14
13
12
11
10
Contents of Word n
Bit
Item
0
Write Bit
(PT to PLC)
1
Read Bit
(PLC to PT)
2
Delete Recipe
Bit
8
Write Com-
pleted Flag
9
Read Com-
pleted Flag
10
Deletion Com-
pleted Flag
15
Error Flag
Contents of Words n+1 to n+3
Word
Item
n+1
File number
n+2
Block number
n+3
Error Code
9
8
7
6
File Number (0 to 99 hex)
File Number (0 to 99 hex)
Error Code
Description
Turn ON this bit to write values set in
a recipe file from the PT to the PLC.
The Write Completed Flag will turn
OFF when this bit turns OFF.
Turn ON this bit to read values set in
a recipe file from the PLC to the PT.
The Read Completed Flag will turn
OFF when this bit turns OFF.
Turn ON this bit to delete a specified
recipe file. The Deletion Completed
Flag will turn OFF when this bit turns
OFF.
Operation Completed Flag
This bit will then turn ON when the
recipe file data has been read.
This bit will then turn ON when the
recipe file data has been deleted.
This flag will turn ON if an error
occurs during data transfer. If the
write, read, or deletion is performed
normally, the Error Flag will turn OFF.
Specify the number of the recipe file to read or write.
Specify the number of blocks to read or write.
An error code will be written here if an error occurs during
data transfer.
0: Normal
ON: The specified file does not exist.
2: The specified block does not exist.
3: Recipe data cannot be written because memory is full.
If the write, read, or deletion is performed normally, the
Error Code will be 0000 hex.
Section 8-5
5
4
3
2
1
Type
Turn ON the opera-
tion bit.
It will then turn ON
when the recipe file
data has been writ-
ten.
Description
0

Advertisement

Table of Contents
loading

This manual is also suitable for:

Nv3w seriesNv4w seriesNv3q series

Table of Contents