Ambient Temperature Effect - Emerson Rosemount 3051S Series Reference Manual

Scalable pressure, flow, and level solution with hart protocol
Hide thumbs Also See for Rosemount 3051S Series:
Table of Contents

Advertisement

Rosemount 3051S Series

Ambient Temperature Effect

Transmitter with Coplanar Sensor Module (Single Variable)
Differential Pressure: (3051S_CD)
Gage Pressure: (3051S_CG)
Ultra
per 50 °F (28 °C)
(2)
Ranges 2 - 5
±(0.009% URL + 0.025% span)
from 1:1 to 10:1;
±(0.018% URL + 0.08% span)
from >10:1 to 200:1
Range 0 ±(0.25% URL + 0.05% span)
from 1:1 to 30:1
Range 1 ±(0.1% URL + 0.25% span)
from 1:1 to 50:1
Absolute Pressure: (3051S_CA)
Ultra
per 50 °F (28 °C)
Ranges 2-4 ±(0.0125% URL + 0.0625%
span) from 1:1 to 5:1;
±(0.025% URL + 0.125% span)
from >5:1 to 200:1
Range 0 ±(0.1% URL + 0.25% span)
from 1:1 to 30:1
Range 1 ±(0.0125% URL + 0.0625%
span) from 1:1 to 5:1;
±(0.025% URL + 0.125% span)
from >5:1 to 100:1
(1) Ultra for Flow is only available for 3051S_CD Ranges 2-3.
(2) Use Classic specification for 3051S_CD Range 5 Ultra.
Transmitter with In-Line Sensor Module
Absolute Pressure: (3051S_TA)
Gage Pressure: (3051S_TG)
Ultra
per 50 °F (28 °C)
Ranges 2-4 ±(0.009% URL + 0.025% span)
from 1:1 to 10:1;
±(0.018% URL + 0.08% span)
from >10:1 to 100:1
Range 5 ±(0.05% URL + 0.075% span)
from 1:1 to 10:1
Range 1 ±(0.0125% URL + 0.0625% span)
from 1:1 to 5:1;
±(0.025% URL + 0.125% span)
from >5:1 to 100:1
Liquid Level Transmitter
3051S_L
A-4
Classic
per 50 °F (28 °C)
±(0.0125% URL +0.0625% span)
from 1:1 to 5:1;
±(0.025% URL + 0.125% span)
from >5:1 to 100:1
±(0.25% URL + 0.05% span)
from 1:1 to 30:1
±(0.1% URL + 0.25% span)
from 1:1 to 50:1
Classic
per 50 °F (28 °C)
±(0.0125% URL + 0.0625% span) from 1:1
to 5:1;
±(0.025% URL + 0.125% span) from >5:1
to 100:1
±(0.1% URL + 0.25% span) from 1:1 to
30:1
±(0.0125% URL + 0.0625% span) from 1:1
to 5:1;
±(0.025% URL + 0.125% span) from >5:1
to 100:1
Classic
per 50 °F (28 °C)
±(0.0125% URL + 0.0625% span)
from 1:1 to 5:1;
±(0.025% URL + 0.125% span)
from >5:1 to 100:1
±(0.05% URL + 0.075% span)
from 1:1 to 10:1
±(0.0125% URL + 0.0625% span)
from 1:1 to 5:1;
±(0.025% URL + 0.125% span)
from >5:1 to 100:1
Ultra
See Instrument Toolkit
Reference Manual
00809-0100-4801, Rev FA
October 2010
(1)
Ultra for Flow
-40 to 185 °F (-40 to 85 °C)
±0.13% of reading up to 8:1 DP turndown
from URL;
±[0.13 + 0.0187(URL/Reading)]% of
reading to 100:1 DP turndown from URL
Not Available
Not Available
Classic
See Instrument Toolkit