Operation - Emerson Rosemount 3051S Series Reference Manual

Scalable pressure, flow, and level solution with hart protocol
Hide thumbs Also See for Rosemount 3051S Series:
Table of Contents

Advertisement

Rosemount 3051S Series

Operation

Device Dashboard
Fast Keys
Figure 7-14. SPM diagnostic can
be activated from the SPM
Status screen
7-16
Low Detection Message
Customizable message field related to standard deviation / coefficient of
variation crossing the lower threshold value. This message can be used to
describe the abnormal process condition or provide additional details for
troubleshooting. Message will appear along with the Low Variation or Low CV
Detected alert. Character limit is 32 including spaces.
Mean Change Message
Customizable message field related to mean value crossing either the upper
or lower threshold value. This message can be used to describe the abnormal
process condition or provide additional details for troubleshooting. Message
will appear along with the Mean Change Detected alert. Character limit is 32
including spaces.
1, 3, 2
Turning On the SPM Diagnostic
The SPM diagnostic is enabled by selecting On for "SPM Mode", shown on
Figure 7-14. Upon enabling SPM, the diagnostic will automatically begin
"Learning" with the following exception: if valid baseline values have been
previously established and "Monitor" has been selected as the option for
Power Interruption on the Baseline Configuration screen, then the diagnostic
will bypass Learning and begin Monitoring immediately. The diagnostic status
will stay in the Learning mode for the Learning Period specified on the
Baseline Configuration screen. After the learning period is complete, the
Mode will change to Verifying and a blue line will appear on the charts
indicating the learned baseline value. Upon completion of the Verify mode, the
diagnostic will use the parameters selected on the Verification Criteria page to
validate the baseline value. After the Verifying period the Mode will switch to
Monitoring and grey lines that indicate the sensitivity setting will appear on the
charts.