Dx80 Is Modbus/Tcp Client/Server (Default) - Banner SureCross DX80 Gateway Pro Reference Manual

Wireless i/o network system web configurator
Hide thumbs Also See for SureCross DX80 Gateway Pro:
Table of Contents

Advertisement

RF Devices Tab
Setting
Gateway
DX80 is Modbus/TCP
Client/Server (default)
DX80 is Modbus RTU
Master
DX80 is Modbus RTU
Slave
22
P/N 134421
Send button: After making changes to parameters on the expanded Configure Point screen, click on
the Send button to send these changes to the device and click on the Change button to send the
changes to the DX83 Ethernet Bridge or the Gateway Pro.
Gateway
Pro
Slave
Master
Master
Master
Slave
Slave

DX80 is Modbus/TCP Client/Server (default)

The default configuration is DX80 is Modbus/TCP Client/Server. The DX83 Ethernet Bridge is
the Modbus master device and only communicates with the device configured as Slave ID 1: the
Gateway.
Node 2
Registers 33-48
Ethernet
Bridge
Master
Default mode. The Gateway is a Modbus slave device and the Ethernet
Bridge is the master device.
Ignored
The Ethernet Bridge can only communicate with a slave device. In
this mode, any communications sent to the Bridge from the Web
Configurator is ignored. To resume communications, cycle power to the
Gateway. When power is cycled, the Ethernet Bridge begins again as a
master device until the timeout lapses.
Ignored
Similar to the default mode, but a device other than the Ethernet
Bridge acts as the Modbus master device. The Ethernet Bridge still
communicates with the Gateway and can read and write to registers, but
another device is the master device.
Node 1
Registers 17-32
Slave ID 1
SureCross™ DX80 Web Configurator
DX80 Gateway
Registers 1-16
Node 3
Registers 49-64
Banner Engineering Corp. • Minneapolis, MN U.S.A.
www.bannerengineering.com • Tel: 763.544.3164
Instruction Manual
DX83 Ethernet Bridge