Banner SureCross DX80 Series Manual

Banner SureCross DX80 Series Manual

Configurable node with 2 discrete inputs, 2 discrete outputs, 2 analog inputs, and 2 analog outputs
Hide thumbs Also See for SureCross DX80 Series:

Advertisement

Quick Links

SureCross DX80 Node
Configurable Node with 2 discrete inputs, 2 discrete outputs, 2 analog inputs, and 2 analog outputs
For additional information, updated documentation, and accessories, refer to Banner Engineering's website,
ing.com/surecross.
Models
DX80N9X6S2P2M2M2
DX80N9X6W2P2M2M2
WARNING: Not To Be Used for Personnel Protection
Never use this device as a sensing device for personnel protection. Doing so could lead to serious
injury or death. This device does not include the self-checking redundant circuitry necessary to allow its
use in personnel safety applications. A sensor failure or malfunction can cause either an energized or de-
energized sensor output condition.
SureCross User Configuration Tool
Setting Up Your Wireless Network
To set up and install your wireless network, follow these steps:
1. Configure the DIP switches of all devices.
2. Connect the sensors to the SureCross devices.
3. Apply power to all devices.
4. Form the wireless network by binding the Nodes to the Gateway. If the binding instructions are not included in the datasheet, refer to
the product manual for binding instructions.
5. Observe the LED behavior to verify the devices are communicating with each other.
6. Conduct a site survey between the Gateway and Nodes. If the site survey instructions are not included in this datasheet, refer to the
product manual for detailed site survey instructions.
P/N 131295 Rev. F
The SureCross® wireless system is a radio frequency network with integrated I/O that can oper-
ate in most environments and eliminate the need for wiring runs. Wireless networks are formed
around a Gateway, which acts as the wireless network master device, and one or more Nodes.
• Wireless industrial I/O device with two selectable discrete inputs, two sourcing discrete out-
puts, two 0 to 20 mA analog inputs, and two 0 to 20 mA analog outputs
• 10 to 30V dc power input
• DIP switches for user configuration
• Frequency Hopping Spread Spectrum (FHSS) technology and Time Division Multiple Access
(TDMA) control architecture ensure reliable data delivery within the unlicensed Industrial, Sci-
entific, and Medical (ISM) band
• Transceivers provide bidirectional communication between the Gateway and Node, including
fully acknowledged data transmission
• Lost RF links are detected and relevant outputs set to user-defined conditions
Frequency
Antenna
External
900 MHz ISM Band
Internal
The User Configuration Tool (UCT) offers an easy way to link I/O points in your wire-
less network, view I/O register values graphically, and set system communication pa-
rameters when a host system is not part of the wireless network.
The UCT requires a special USB to RS-485 (model number BWA-UCT-900 for 1 Watt
radios, BWA-HW-006 can be used for all other radios) converter cable to pass infor-
mation between your computer and the Gateway. Download the most recent revi-
sions of the UCT software from Banner Engineering's website:
gineering.com/wireless.
5/21/2013
I/O
Inputs: Two selectable discrete, two 0 to 20 mA analog
Outputs: Two sourcing discrete, two 0 to 20 mA analog
www.bannerengineer-
http://www.banneren-
0 131295
9

Advertisement

Table of Contents
loading

Summary of Contents for Banner SureCross DX80 Series

  • Page 1 • Transceivers provide bidirectional communication between the Gateway and Node, including fully acknowledged data transmission • Lost RF links are detected and relevant outputs set to user-defined conditions For additional information, updated documentation, and accessories, refer to Banner Engineering's website, www.bannerengineer- ing.com/surecross.
  • Page 2: Configuring The Dip Switches

    For additional information, including installation and setup, weatherproofing, device menu maps, troubleshooting, and a list of accesso- ries, refer to one of the following product manuals. • SureCross Quick Start Guide: Banner part number 128185 • SureCross Wireless I/O Network Manual: 132607 •...
  • Page 3 SureCross DX80 Node Address Mode The SureCross wireless devices may use one of two types of addressing modes: rotary dial addressing or extended addressing. In rotary dial address mode, the left rotary dial establishes the network ID and the right rotary dial sets the device ID. The wireless network is restricted to a maximum of 16 devices.
  • Page 4 SureCross DX80 Node Terminal Block AIx or Ax. Analog IN x. AOx. Analog OUT x. DIx. Discrete IN x. DOx. Discrete OUT x. GND. Ground/dc common connection. PWR. Power, 10 to 30V dc power connection. Wiring Diagrams for Discrete Inputs Connecting dc power to the communication pins will cause permanent damage.
  • Page 5: Led Behavior For The Nodes

    SureCross DX80 Node Analog Input Wiring (10 to 30V dc Pow- Analog Input Wiring (4–20mA, 2-Wire, Analog Input Wiring (4–20mA, 2-Wire, Externally Powered Sensors) Switch Powered Sensors) − 10-30V dc external power sensor − − − sensor sensor dc common dc common dc common (Only possible in models with switch power...
  • Page 6: Specifications

    SureCross DX80 Node I/O # Modbus Holding Register I/O Type Units I/O Range Holding Register Terminal Representation Block Labels Gateway Any Node Min. Val- Max. Val- Min. Max. (Dec.) (Dec.) 7 + (Node# × 16) Reserved 8 + (Node# × 16) Device Message 9 + (Node# ×...
  • Page 7 SureCross DX80 Node Inputs and Outputs Discrete Input ON Condition Discrete Output Rating (PNP) PNP: Greater than 8V 100 mA max current at 30V dc NPN: Less than 0.7V ON-State Saturation: Less than 3V at 100 mA Discrete Input OFF Condition OFF-state Leakage: Less than 10 μA PNP: Less than 5V Analog Outputs...
  • Page 8: Banner Engineering Corp Limited Warranty

    ER ARISING IN CONTRACT OR WARRANTY, STATUTE, TORT, STRICT LIABILITY, NEGLIGENCE, OR OTHERWISE. Banner Engineering Corp. reserves the right to change, modify or improve the design of the product without assuming any obligations or liabilities relating to any product previously manufactured by Banner Engineering Corp.