SureCross™ DX80 Web Configurator
System Tab
Instruction Manual

Cascade

Use the Cascade tab to configure the cascading of the registers: data from the source register is
copied to the destination register(s).
Enter the single destination register or a range of destination registers to copy the source
register to. If no last destination register is entered, only a single destination register is used.
Do not use the same source register more than once in the cascade rules. To copy a register's
contents to multiple, non-consecutive registers, only use the primary source register once. To copy
the same contents to additional registers, use the previous destination register as the second rule's
source register and 'daisy-chain' the register contents. For example, do not create three rules to
copy register 5's contents to register 6, 14, and 18. Instead, create one rule to copy register 5's
contents to register 6, a second rule to copy register 6's contents to register 14, and a third rule to
copy register 14's contents to register 18.
Entering a zero as a source register negates the rule even though it remains in the list until deleted.
Unused rules at the end of the list always show zero as the source register. To prevent these from
displaying, reduce the number of rules enabled.
Other Commands
Delete button: Removes the rule number listed in the Showing box.
Insert button: Inserts a new rule number in front of the rule number listed in the Showing box.
Prev and Next buttons: Displays the next rule.
Update button: Sends new data or settings to the Ethernet Bridge or Gateway Pro.

Calculate

Use the Calculate tab to set up simple calculations on the register data.
Entering none as the operation negates the rule even though it remains in the list until deleted.
Unused rules at the end of the list always show none as the operation. To prevent these from
displaying, reduce the number of rules enabled.
To establish calculations, select the operation from the drop list. All operations except logical NOT
operations require two operands. Enter the register numbers as applicable. Some operations are
valid for ranges of registers. Select and or thru to select two registers or multiple registers in a
range. Average, sum, and logic operations are valid for ranges of multiple registers.
Banner Engineering Corp. • Minneapolis, MN U.S.A.