Led Behavior For The Nodes; Modbus Register Table; Specifications - Banner SureCross DX80 Series Manual

Configurable node with analog inputs and analog outputs
Hide thumbs Also See for SureCross DX80 Series:
Table of Contents

Advertisement

SureCross DX80 Node
Analog Output Wiring
PWR
AOx
sensor
GND

LED Behavior for the Nodes

After powering up and binding the Gateway and its Nodes, verify all devices are communicating properly. A Node will not sample its
inputs until it is communicating with its Gateway. When testing communication between the Gateway and Node, all radios and antennas
should be at least two meters apart or the communications may fail.
LED 1
(flashing green)
(flashing red)

Modbus Register Table

I/O
Modbus Holding Register
Gateway /
Any Node
DX85
1
1
1 + (Node# × 16)
2
2
2 + (Node# × 16)
3
3
3 + (Node# × 16)
4
4
4 + (Node# × 16)
...
7
7
7 + (Node# × 16)
8
8
8 + (Node# × 16)
9
9
9 + (Node# × 16)
10
10
10 + (Node# × 16)
11
11
11 + (Node# × 16)
12
12
12 + (Node# × 16)
...
15
15
15 + (Node# × 16)
16
16
16 + (Node# × 16)

Specifications

P/N 136326 Rev. E
10-30V dc
dc common
LED 2
(flashing red)
(flashing red, 1 per 3 sec)
I/O Type
Units
Analog IN 1
Analog IN 2
Analog IN 3
Analog IN 4
Reserved
Device Message
Analog OUT 1
Analog OUT 2
Analog OUT 3
Analog OUT 4
Control Message
Reserved
www.bannerengineering.com - tel: 763-544-3164
Node Status
Radio Link Ok
Device Error
No Radio Link
I/O Range
Min.
Max.
mA / V
0.0
20.0 / 10.0
mA / V
0.0
20.0 / 10.0
mA / V
0.0
20.0 / 10.0
mA / V
0.0
20.0 / 10.0
mA / V
0.0
20.0 / 10.0
mA / V
0.0
20.0 / 10.0
mA / V
0.0
20.0 / 10.0
mA / V
0.0
20.0 / 10.0
Holding Register Rep-
Terminal
resentation
Block Labels
Min. (Dec.) Max.
(Dec.)
0
65535
0
65535
0
65535
0
65535
0
65535
0
65535
0
65535
0
65535
AI1
AI2
AI3
AI4
AO1
AO2
AO3
AO4
5