Initial Setting; Setting Of Switches In Upper Link Unit - Mitsubishi A953GOT-SBD-M3-H Hardware Manual

Table of Contents

Advertisement

A953 HANDY GOT
8.2

Initial setting

8.2.1

Setting of switches in upper link unit

When using the upper link unit (C200H-LK201-V1 or C500H-LK201-V1), set the switches as
shown below.
1) When the C200H-LK201-V1 is used
Setting of switches on
the front face
LK201-V1
RUN
RCV
SW1
SW3
Setting of switches on
the rear face
XM
ERROR
SW2
SW4
a) Setting of the SW1 and the SW2
(setting of the unit No.)
Set "SW1: 0, SW2: 0" (to set the unit No. 00).
b) Setting of the SW3
(setting of the transmission speed)
Set "SW3: 6" (to set 19,200 bps).
c) Setting of the SW4
(setting of the command level, the parity and
the transmission code)
Set "SW4: 2"
(to set even parity, 7 ASCII bits and 2 stop bits).
d) Setting of the 5 V supply SW
When using the optical interface Z3RN-A-5, set
this switch to ON (5V supply provided).
When not using the optical interface, make sure
to set it to OFF.
SW No.
ON
1
(To be set to OFF.)
2
"1:N" procedure
3
4
5 V supply provided 5 V supply not provided
e) CTS selector SW
Set this switch to the "0 V" side to always keep
the CTS at ON. Set this switch to the "external"
side to receive signal from the outside.
Usually, set this switch to the "0 V" side.
Connection to PLC by Omron 8
OFF
Not used
"1:1" procedure
8-4