A953 HANDY GOT
7.2

Initial setting

7.2.1

Setting in communication link unit and serial communication unit

When connecting the GOT to a computer link unit or serial communication unit for monitoring,
set the switches of the computer link unit or the serial communication unit as shown below.
1) When the QJ71C24(-R2) is connected
Set the switches of the QJ71C24(-R2) using the I/O assignment setting of the GPPW. For
the details of the setting method, refer to the GPPW OPERATING MANUAL.
The contents of setting vary depending on the CH (interface number) of the serial
communication unit connected to the GOT.
Set the switches in accordance with the connected CH as follows.
CH connected to GOT
Point
When the GOT is connected, the CH1 and the CH2 of the serial communication unit cannot
be used at the same time. Accordingly, have in mind that both the GOT and peripheral
equipment having the GPP function cannot be connected at the same time to one serial
communication unit and that two GOT units cannot be connected to one serial
communication unit at the same time.
CH1
CH2
Computer Link Connection 7
Contents of setting
7-2