Commissioning a project
6.6 Updating the operating system - Basic Panel DP
6.6.2

Resetting the factory settings

In ProSave or WinCC, you can update the operating system with or without resetting to
factory settings.
● Updating the operating system without reset to factory settings
First, switch into "Transfer" mode on the HMI device or use the automatic transfer
function if the project is active. Then start the operating system update in ProSave or
WinCC.
● Updating the operating system with reset to factory setting
Note
Data channel
When resetting to factory settings, all data channel parameters used are reset. The
transfer can only be started following reconfiguration of the data channel.
See also
Data transmission options (Page 75)
6.6.3

Updating the operating system using ProSave

Requirement
● The HMI device is connected to a PC on which ProSave is installed.
● The data channel parameters are assigned on the HMI device.
Procedure
1. From the Windows start menu, start ProSave on the PC.
2. Select the HMI device type in the "General" tab.
3. Select the type of connection between the HMI device and the PC, then set the
connection parameters.
4. Select the "OS Update" tab.
5. Select whether to update the operating system with or without restoring the factory
settings by setting the "Reset to factory settings" check box accordingly.
84