8.9
Scope of functions with WinCC
The following tables show the objects that can be integrated in a project for a Basic Panel.
The following tables support you in estimating whether your project is still within the
performance features of the HMI device.
The specified maximum values are not additive. We cannot guarantee proper functioning of
configurations on devices in which all system limits are exploited.
In addition to the limitations specified, allowances must also be made for restrictions in
configuration memory resources.
Tags, values and lists
Object
Tags
Limit value monitoring
Linear scaling
Elements per array
Text lists
Graphics lists
Alarms
Object
Alarms
Alarm buffer
Basic Panels 2nd Generation
Operating Instructions, 10/2016, A5E33293231-AB
Specification
Quantity
Input/output
Input/output
Quantity
Quantity
Quantity
Specification
Number of alarm classes
Number of discrete alarms
Number of analog alarms
Length of the alarm text
Number of tags in an alarm
Display
Acknowledge error alarm individually
Acknowledge multiple error alarms simultaneously
(group acknowledgement)
Edit alarm
Alarm indicator
Alarm buffer capacity
Simultaneously queued alarm events
View alarm
Delete alarm buffer
Technical specifications
8.9 Scope of functions with WinCC
Quantity
800
Yes
Yes
100
300
100
Quantity
32
1000
25
80 characters
Max. 8
Alarm window, alarm view
Yes
16 acknowledgment groups
Yes
Yes
256 alarms
Max. 64
Yes
Yes
115