Cooling Operation Fan Control - Daikin R410As Service Manual

Vrv heat pump 50hz
Table of Contents

Advertisement

Si39-302
2.4

Cooling Operation Fan Control

In cooling operation with low outdoor air temperature, this control is used to provide the
adequate amount of circulation air with liquid pressure secured by high pressure control using
outdoor unit fan.
Pc<2.8 MPa
Pc>3.1 MPa
Pc<1.8 MPa
Pc<1.8 MPa
Pc<1.8 MPa
Pc<1.8 MPa
Pc<1.8 MPa
Pc<1.8 MPa
Pc<2.3 MPa
Function
STEP9
Pc>3.3 MPa
STEP8
Pc>2.7 MPa
STEP7
Fan Steps
Pc>2.7 MPa
STEP6
Pc>2.7 MPa
STEP5
Pc>2.7 MPa
STEP4
Pc>2.7 MPa
STEP3
Pc>2.7 MPa
STEP2
Pc>2.7 MPa
STEP1
Pc: HP pressure sensor detection value
RXYQ5M
8 and 10M
STEP1
0rpm
STEP2
300rpm
STEP3
320rpm
STEP4
340rpm
STEP5
370rpm
STEP6
440rpm
STEP7
535rpm
STEP8
515rpm
STEP9
750rpm
Basic Control
RXYQ
RXYQ
12 to 16M
0rpm
0rpm
300rpm
300rpm
320rpm
325rpm
345rpm
355rpm
385rpm
400rpm
465rpm
500rpm
575rpm
630rpm
785rpm
880rpm
825rpm
920rpm
73