Daikin R410As Service Manual page 129

Vrv heat pump 50hz
Table of Contents

Advertisement

Field Setting
There are the following three setting modes.
$
Initial status (when normal) : Used to select the cool/heat setting. Also indicates during
"abnormal", "low noise control" and "demand control".
%
Used to modify the operating status and to set program addresses, etc. Usually used in
servicing the system.
&
Used to check the program made in Setting mode 2.
!
!
Press BS1 (MODE button) for more than 5 sec.
Setting mode 2
Setting item selection (Set)
Press BS3
(RETURN button).
Setting condition
selection (Set)
Press BS3
(RETURN button).
Setting condition
(Contents) display
Press BS3
(RETURN button).
Press BS1
(MODE button).
118
Setting mode 1 (H1P off)
Setting mode 2 (H1P on)
Monitor mode (H1P blinks)
Mode changing procedure
Using the MODE button, the modes can be changed as follows.
Push and hold the BS1
(MODE button) for 5 seconds.
Setting mode 2
Push the BS1(MODE button) one time.
MODE
On
H1P
Mode changing procedure
BS1
BS2
BS3
BS4
MODE
SET
RETURN
TEST
(Normal)
Setting mode 1
MODE
Off
H1P
(Set): Select mode with BS2 (SET button) in each selection step.
Setting mode 1
Press BS1(MODE button).
(Initial condition)
BS5
RESET
(V2760)
Push the BS1(MODE button)
one time.
Monitor mode
MODE
H1P
Monitor mode
Check item selection (Set)
Press BS3
(RETURN button).
Contents display
Press BS3
(RETURN button).
Press BS1
(MODE button).
Test Operation
Si39-302
Blinking
(V2761)
(V2762)