F3" Outdoor Unit: Abnormal Discharge Pipe Temperature - Daikin R410As Service Manual

Vrv heat pump 50hz
Table of Contents

Advertisement

Troubleshooting by Indication on the Remote Controller
2.20 " F3 " Outdoor Unit:
Temperature
F3
Remote
Controller
Display
Applicable
RXYQ5~48M
Models
Method of
Abnormality is detected according to the temperature detected by the discharge pipe
temperature sensor.
Malfunction
Detection
!
Malfunction
!
Decision
Conditions
!
Supposed
!
Causes
!
Troubleshooting
2: Refer to thermistor resistance / temperature characteristics table on P280.
180
Abnormal Discharge Pipe
When the discharge pipe temperature rises to an abnormally high level
When the discharge pipe temperature rises suddenly
Faulty discharge pipe temperature sensor
Faulty connection of discharge pipe temperature sensor
Faulty outdoor unit PCB
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
Discharge pipe
temperature is 115˚C
or higher.
NO
Are
the characteristics
of the discharge pipe
thermistor normal?
(3.5~400KΩ)
YES
YES
NO
Si39-302
Out of gas, compression defect,
etc. Defect of the refrigerant
system.
Replace the discharge pipe
thermistor.
Replace outdoor unit PC board
A2P.