Cooling Operation Fan Control - Daikin ERQ Service Manual

Erq 100/125/140 a7v1b (outdoor unit) ekeqd/f/mcbv3 (control box) ekexv 50/63/80/100/125/140 (expansion valve kit)
Hide thumbs Also See for ERQ:
Table of Contents

Advertisement

ESIE09-05
2.3

Cooling Operation Fan Control

In cooling operation with low outdoor air temperature, this control is used to provide the
adequate amount of circulation air with liquid pressure secured by high pressure control using
outdoor unit fan.
Furthermore, when outdoor temperature ≥ 20°C, the compressor will run in Step 7 or higher.
When outdoor temperature ≥ 18°C, it will run in Step 5 or higher.
When outdoor temperature ≥ 12°C, it will run in Step 1 or higher.
-1 step on
outdoor unit fan
Fan Steps
Cooling
STEP0
STEP1
STEP2
STEP3
STEP4
STEP5
STEP6
STEP7
STEP8
Function
Upper limit of fan
revolutions: Step 8
Pc < 2.75MPa
Upper limit of outdoor unit
fan revolutions
Step 7
PI control
Lapse of 20 sec.
Hold the
current step on
outdoor unit fan
PI control
M1F
M2F
0 rpm
0 rpm
250 rpm
0 rpm
400 rpm
0 rpm
285 rpm
250 rpm
360 rpm
325 rpm
445 rpm
410 rpm
580 rpm
545 rpm
715 rpm
680 rpm
850 rpm
815 rpm
Pc: HP pressure sensor detection value
Pc > 3.24MPa
PI control
+1 step on
outdoor unit fan
Lapse of 20 sec.
: http://splitoff.ru/tehn-doc.html
Basic Control
25