Basic Control
2.4

Cooling Operation Fan Control

In cooling operation with low outdoor air temperature, this control is used to provide the
adequate amount of circulation air with liquid pressure secured by high pressure control using
outdoor unit fan.
Pc<2.8MPa
Pc>3.1MPa
Pc<2.7MPa
Pc<1.8MPa
Pc<1.8MPa
Pc<1.8MPa
Pc<1.8MPa
Pc<1.8MPa
Pc<1.8MPa
Pc<2.3MPa
84
STEP9
Pc>3.3MPa
STEP8-1
Pc>3.2MPa
STEP8-2
Pc>2.7MPa
STEP7
Pc>2.7 MPa
STEP6
Pc>2.7 MPa
STEP5
Pc>2.7 MPa
STEP4
Pc>2.7 MPa
STEP3
Pc>2.7 MPa
STEP2
Pc>2.7 MPa
STEP1
Pc: HP pressure sensor detection value
Fan Steps
RXYQ5M
STEP1
0rpm
STEP2
300rpm
STEP3
320rpm
STEP4
350rpm
STEP5
385rpm
STEP6
470rpm
STEP7
585rpm
STEP8-2
800rpm
STEP8-1
800rpm
STEP9
840rpm
SiE39-404
RXYQ
RXYQ
8 and 10M
12 to 16M
0rpm
0rpm
300rpm
300rpm
320rpm
325rpm
345rpm
355rpm
385rpm
400rpm
465rpm
500rpm
575rpm
630rpm
660rpm
710rpm
785rpm
880rpm
825rpm
920rpm
Function