Daikin R410As Service Manual page 39

Vrv heat pump 50hz
Table of Contents

Advertisement

Specifications
Ceiling Mounted Built-in Type
Model
#
1 Cooling Capacity (19.5°CWB)
#
2 Cooling Capacity (19.0°CWB)
# # # #
3 Heating Capacity
Casing
Dimensions: (H×W×D)
Rows×Stages×Fin Pitch
Coil (Cross
Fin Coil)
Face Area
Model
Type
Motor Output × Number of
Units
Fan
Air Flow Rate (H/L)
# # # #
4 Static external
pressure
Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Liquid Pipes
Piping
Gas Pipes
Connections
Drain Pipe
Machine Weight
# # # #
7 Sound Level (H/L) (220V)
Safety Devices
Refrigerant Control
Connectable outdoor unit
Model
Decoration
Panel Color
Panel
Dimensions: (H×W×D)
(Option)
Weight
Standard Accessories
Drawing No.
Notes:
#
1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m,
#
2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m,
#
3 Indoor temp. : 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length; 7.5m,
#
4 Static external pressure is changeable to change over the connectors inside electrical box, this pressure
#
5 Static external pressure is changeable to change over the connectors inside electrical box, this pressure
6 Capacities are net, including a deduction for cooling (an additional for heating) for indoor fan motor heat.
#
7 Anechoic chamber conversion value, measured at a point 1.5m downward from the unit center. These
28
FXSQ20MVE
kcal/h
2,000
Btu/h
7,900
kW
2.3
kW
2.2
kcal/h
2,200
Btu/h
8,500
kW
2.5
Galvanized Steel Plate
mm
300×550×800
mm
3×14×1.75
0.088
D18H3A
Sirocco Fan
W
50×1
m³/min
9/6.5
Pa
88-39-20
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Glass Fiber
Resin Net (with Mold Resistant)
φ
mm
6.4 (Flare Connection)
φ
mm
12.7 (Flare Connection)
VP25
mm
(External Dia. 32 Internal Dia. 25)
kg
30
dBA
37/32
Fuse,
Thermal Protector for Fan Motor
Electronic Expansion Valve
R410A M Series
BYBS32DJW1
White (10Y9/0.5)
mm
55×650×500
kg
3
Operation Manual, Installation
Manual, Paper Pattern for Installation,
Drain Hose, Clamp Metal, Insulation
for Fitting, Sealing Pads, Clamps,
Screws, Washers.
level difference: 0m.
level difference: 0m.
level difference; 0m. (Heat pump only)
means "High static pressure-Standard -Low static pressure".
means "High static pressure-Standard".
values are normally somewhat higher during actual operation as a result of installation conditions.
FXSQ25MVE
2,500
9,900
2.9
2.8
2,800
10,900
3.2
Galvanized Steel Plate
300×550×800
3×14×1.75
0.088
D18H3A
Sirocco Fan
50×1
9/6.5
88-39-20
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Glass Fiber
Resin Net (with Mold Resistant)
φ
6.4 (Flare Connection)
φ
12.7 (Flare Connection)
VP25
(External Dia. 32 Internal Dia. 25)
30
37/32
Fuse,
Thermal Protector for Fan Motor
Electronic Expansion Valve
R410A M Series
BYBS32DJW1
White (10Y9/0.5)
55×650×500
3
Operation Manual, Installation
Manual, Paper Pattern for Installation,
Drain Hose, Clamp Metal, Insulation
for Fitting, Sealing Pads, Clamps,
Screws, Washers.
3D039431
Si39-302
FXSQ32MVE
3,150
12,500
3.7
3.6
3,400
13,600
4.0
Galvanized Steel Plate
300×550×800
3×14×1.75
0.088
D18H3A
Sirocco Fan
50×1
9.5/7
64-39-15
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Glass Fiber
Resin Net (with Mold Resistant)
φ
6.4 (Flare Connection)
φ
12.7 (Flare Connection)
VP25
(External Dia. 32 Internal Dia. 25)
30
38/32
Fuse,
Thermal Protector for Fan Motor
Electronic Expansion Valve
R410A M Series
BYBS32DJW1
White (10Y9/0.5)
55×650×500
3
Operation Manual, Installation
Manual, Paper Pattern for Installation,
Drain Hose, Clamp Metal, Insulation
for Fitting, Sealing Pads, Clamps,
Screws, Washers.
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
Specifications

Hide quick links:

Advertisement

Table of Contents
loading