U1" Reverse Phase, Open Phase - Daikin R410As Service Manual

Vrv heat pump 50hz
Table of Contents

Advertisement

Troubleshooting by Indication on the Remote Controller
2.39 " U1 "
Reverse Phase, Open Phase
U1
Remote
Controller
Display
#
Applicable
Models
Method of
Detection is based on the voltage in main circuit capacitor for inverter and supply voltage.
The phase of each phase are detected by reverse phase detection circuit and right phase or
Malfunction
reverse phase are judged.
Detection
Malfunction
Decision
Conditions
!
Supposed
!
Causes
!
Troubleshooting
200
3 phase outdoor unit only
Power supply reverse phase
Power supply open phase
Defect of outdoor PC board A1P
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
There
is an open phase
at the power supply
terminal section (X1M)
of the outdoor
unit.
NO
Operation
is normal if one
place of power supply
line phase is
replaced.
NO
YES
YES
Si39-302
Fix the open phase. Requires
inspection of field power supply
section.
Reverse phase
Counter measure of the problem is
completed by phase replacement.
Replace outdoor unit PC board
A1P.
(V2820)
Troubleshooting