Mc" Address Duplication, Improper Setting - Daikin R410As Service Manual

Vrv heat pump 50hz
Table of Contents

Advertisement

Troubleshooting (OP: Schedule Timer)
" MC "
4.5
Address Duplication, Improper Setting
MC
Remote
Controller
Display
Applicable
All models of indoor units,
Models
schedule timer
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
!
Supposed
Causes
Troubleshooting
230
Address duplication of optional controller for centralized control
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
Are two or more
centralized controller
connected?
NO
YES
Si39-302
Disconnect all centralized
controller except one and reset
the centralized controller timer's
power supply.
Reset the power supply for the
centralized controller.
(V2840)
Troubleshooting