Pump-Down Residual Operation - Daikin R410As Service Manual

Vrv heat pump 50hz
Table of Contents

Advertisement

Special Control
3.4

Pump-down Residual Operation

3.4.1 Pump-down Residual Operation in Cooling Operation
Actuator
Compressor
Outdoor unit fan
Four way valve
Main motorized valve (EV1)
∗Value in ( ) are for RXYQ5M only.
Subcooling motorized valve (EV2)
Hot gas bypass valve (SVP)
Oil equalization valve (SVO)
Receiver gas charging valve (SVL)
Receiver gas discharging valve (SVG)
Non-operating unit gas discharging
valve (SVSG)
Non-operating unit liquid pipe stop
valve (SVSL)
Ending conditions
* Actuators are based on RXYQ16M.
3.4.2 Pump-down Residual Operation in Heating Operation
Actuator
Compressor
Outdoor unit fan
Four way valve
Main motorized valve (EV1)
Subcooling motorized valve (EV2)
Hot gas bypass valve (SVP)
Oil equalization valve (SVO)
Receiver gas charging valve (SVL)
Receiver gas discharging valve (SVG)
Non-operating unit gas discharging
valve (SVSG)
Non-operating unit liquid pipe stop
valve (SVSL)
Ending conditions
* Actuators are based on RXYQ16M.
78
Master unit operation
210 Hz + OFF + OFF
Fan control
OFF
0 pls (1400pls)
0 pls
ON
ON
OFF
ON
OFF
ON
• 5 min.
• Pe<0.5 MPa
or
• Td>110°C
Master unit operation
124 Hz + OFF + OFF
STEP8
ON
0 pls
0 pls
ON
ON
OFF
ON
OFF
ON
• 30 sec.
• Pe<0.25 MPa
or
• Td>110°C
Slave unit operation
OFF
OFF
OFF
0 pls
0 pls
OFF
OFF
OFF
ON
ON
ON
Slave unit operation
OFF
STEP5
ON
0 pls
0 pls
OFF
OFF
OFF
ON
ON
ON
Si39-302
Function

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents