P1" Outdoor Unit: Inverter Over-Ripple Protection - Daikin R410As Service Manual

Vrv heat pump 50hz
Table of Contents

Advertisement

Si39-302
2.36 " P1 " Outdoor Unit:
P1
Remote
Controller
Display
Applicable
RXYQ5~48M
Models
Method of
Imbalance in supply voltage is detected in PC board.
Malfunction
Detection
Malfunction
When the resistance value of thermistor becomes a value equivalent to open or short circuited
status.
Decision
!
Conditions
!
Supposed
!
Causes
!
!
!
!
Troubleshooting
Troubleshooting
Inverter Over-Ripple Protection
Malfunction is not decided while the unit operation is continued.
"P1" will be displayed by pressing the inspection button.
Open phase
Voltage imbalance between phases
Defect of main circuit capacitor
Defect of inverter PC board
Defect of K1M
Improper main circuit wiring
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
Imbalance
in supplied voltage is
in excess of 14 V
(Y1). ∗1
NO
Is
the voltage
imbalance applied to the
inverter in excess of
14 V (Y1)?
∗2
NO
<When voltage monitoring is possible:>
Using a device capable of
constant recording of power
supply voltage record
power supply voltage
between 3 phases (L1 ~ L2,
L2 ~ L3, L3~L1) for about
one continuous week.
Power supply voltage imbalance
∗In accordance with "notification of inspection results" accompanying spare parts.
Explanation for users
Give the user a copy of "notification of inspection results"and leave
it up to him to improve the imbalance.
Troubleshooting by Indication on the Remote Controller
YES
Open phase?
NO
YES
∗1. Measure voltage at the X1M power supply
terminal block.
∗2. Measure voltage at terminals L1, L2 and L3 of
the diode module inside the inverter while the
compressor is running.
measure
YES
Open phase
Normalize field cause.
Fix power supply voltage
imbalance.
Part or wiring defect
After turning the power supply
OFF, check and repair the
main circuit wiring or parts.
(1) Loose or disconnected
wiring between power
supply and inverter
(2) K1M contact disposition,
fusion or contact is poor.
(3) Loose or disconnected
noise filter
Be sure to explain to the user that
there is a "power supply imbalance"
for which DAIKIN is not responsible.
(V2816)
197

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents