Specifications
Wall Mounted Type
Model
# # # #
1 Cooling Capacity (19.5°CWB)
# # # #
2 Cooling Capacity (19.0°CWB)
# # # #
3 Heating Capacity
Casing Color
Dimensions: (H×W×D)
Rows×Stages×Fin Pitch
Coil (Cross
Fin Coil)
Face Area
Model
Type
Motor Output × Number
of Units
Fan
Air Flow Rate (H/L)
Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Liquid Pipes
Piping
Gas Pipes
Connections
Drain Pipe
Machine Weight
# # # #
5 Sound Level (H/L)
Safety Devices
Refrigerant Control
Connectable outdoor unit
Standard Accessories
Drawing No.
Notes:
#
1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m,
#
2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp.: 35°CDB / Equivalent piping length:7.5m,
#
3 Indoor temp. : 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length; 7.5m,
4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
#
5 Anechoic chamber conversion value, measured under JISB8616 conditions. During actual operation,
34
FXAQ20MVE
kcal/h
2,000
Btu/h
7,900
kW
2.3
kW
2.2
kcal/h
2,200
Btu/h
8,500
kW
2.5
White (10Y9/0.5)
mm
290×795×230
mm
2×14×1.4
0.161
Cross Flow Fan
W
40×1
m³/min
7.5/4.5
cfm
265/159
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Foamed Polystyrene /
Foamed Polyethylene
Resin Net (Washable)
φ
mm
6.4 (Flare Connection)
φ
mm
12.7 (Flare Connection)
VP13
mm
(External Dia. 18 Internal Dia. 13)
kg
11
dBA
35/29
Fuse
Electronic Expansion Valve
R410A M Series
Operation Manual, Installation
Manual, Installation Panel, Paper
Pattern for Installation, Insulation
Tape, Clamps, screws.
level difference: 0m.
level difference: 0m.
level difference; 0m. (Heat pump only)
these values are normally somewhat higher as a result of installation conditions.
FXAQ25MVE
2,500
9,900
2.9
2.8
2,800
10,900
3.2
White (10Y9/0.5)
290×795×230
2×14×1.4
0.161
Cross Flow Fan
40×1
8/5
282/177
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Foamed Polystyrene /
Foamed Polyethylene
Resin Net (Washable)
φ
6.4 (Flare Connection)
φ
12.7 (Flare Connection)
VP13
(External Dia. 18 Internal Dia. 13)
11
36/29
Fuse
Electronic Expansion Valve
R410A M Series
Operation Manual, Installation
Manual, Installation Panel, Paper
Pattern for Installation, Insulation
Tape, Clamps, screws.
Si39-302
FXAQ32MVE
3,150
12,500
3.7
3.6
3,400
13,600
4.0
White (10Y9/0.5)
290×795×230
2×14×1.4
0.161
Cross Flow Fan
40×1
9/5.5
318/194
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Foamed Polystyrene /
Foamed Polyethylene
Resin Net (Washable)
φ
6.4 (Flare Connection)
φ
12.7 (Flare Connection)
VP13
(External Dia. 18 Internal Dia. 13)
11
37/29
Fuse
Electronic Expansion Valve
R410A M Series
Operation Manual, Installation
Manual, Installation Panel, Paper
Pattern for Installation, Insulation
Tape, Clamps, screws.
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
Specifications