Specification; Power Requirements; General; Relay Specification - Resource Data Management PR0750-TDB Installation & User Manual

Intuitive mercury tdb controller
Table of Contents

Advertisement

Intuitive Mercury 6-5M Controller with TDB

Power requirements

Supply Voltage Range
Supply Frequency
Maximum supply current
Typical supply current

General

Operating temperature range
Storage temperature range
Environmental
Size
Approx Weight
Safety
EMC
Ventilation
Class 2 Insulation
Supply Fuse
Or MCB
Relay Fuse
Relay

Specification

Mechanical Relays
Max current
Max voltage
Relay Fuse
Solid State Relays (if fitted)
Max current
Max voltage
Daughter Card Specification (If used)
4-20mA Input / Output
Input:
4-20mA current loop, use the 12Vdc output to feed the 4-20mA device.
The 4-20mA output will not operate correctly if the target device input impedance is > 75Ω
Output:
0-5 or 0-10V Input / Output
Input:
Output:
Probe Input
Inputs:
Pulse Input
Reader Specification:
Note: The controller saves the current pulse counts to non-volatile memory every 12 hours.
Warning
Ensure that all power is
switched off before
installing or maintaining
this product
Specification
100 - 240 Vac ±10%
50 - 60 Hz
2 Amps
<1 Amp
0
0
-10
C to +60
C
0
0
-20
C to +65
C
Indoor use at altitudes up to 2000m, pollution degree 1, installation category II. Voltage fluctuations
not to exceed ±10% of nominal voltage.
157mm (W) x 67mm (H) x 120 (D)
500 grams
EN61010
EN61326; 1997 +Amdt. A1; 1998
There is no requirement for forced cooling ventilation
No protective Earth is required and none should be fitted
Built in fuse holder, fuse 2A 240Vac Anti-surge (T) HRC conforming to IEC60127, 32 x 6.3mm
2A, 240 VAC Type C conforming to BS EN 60898 (Note: controller has integral 2A fuse)
10A 240Vac Anti-surge (T) HRC conforming to IEC60127, 32 x 6.3mm
10A Resistive (CosØ = 1)
3A Inductive ( CosØ = 0.4)
250Vac. 30V dc
10A 240Vac Anti-surge (T) HRC conforming to IEC60127, 32 x 6.3mm
1.5A
280Vac (ac only, will not switch dc)
Connect a 0-5 or 0-10V Signal, a 5V supply is provided to feed the sensor.
The output will not operate correctly if the target device input impedance is < 10KΩ.
A 50mA fuse is recommended for this output.
3.01K Ohms
0V Return
Pulse High Duration:
Pulse Low Duration:
Pulse Voltage:
Intuitive Mercury TDB Controller
100ms minimum
100ms minimum
0v return from reader
Revision 2.6
Page 48 of 53
www.resourcedm.com