Resource Data Management PR0750-TDB Installation & User Manual page 52

Intuitive mercury tdb controller
Table of Contents

Advertisement

Intuitive Mercury 6-5M Controller with TDB
to set the controllers 'real time clock'. Note: when connected to a DMTouch, the time will automatically sync itself.
Click on
Time
When the controller is used as a standalone device and not connected to a network (e.g. DM), the RTC will automatically follow the British
Sumer Time Zone as long as the below string is present;
Selecting
allows you to set the logging period.
Config
You can select 15 minutes, 30 minutes or 60 minutes.
15 minutes will log on the hour and every 15 minutes thereafter
30 minutes will log on the hour and on the half hour
60 minutes will log on the hour every hour
The amount of log data stored within the controller is dependent on the number of I/O used in your TDB program and the logging period
selected. For example the controller can record up to 7 days of log data, with a 15 minute sample rate, when up to 63 inputs/outputs are used
within the TDB.
Parameters
Selecting
Selecting
Default Parameters
Name
Selecting
allows you to set in a name for the controller/program
Selecting
Get Log
will display the log from midnight to present time. See Note: below
To get data for a specific period you can edit the web browser URL
http://xxx.xxx.xxx.xxx/log.htm?Start=hhmmddMMyy&End=hhmmddMMyy
Where: -
xxx
Is the IP address of the controller
hh
hours
mm
minutes
dd
day
MM
month
yy
year (11 for year 2011)
Note that there is a start time and an end time.
You could use a start time only and it will show data from the start time entered till the present time
http://xxx.xxx.xxx.xxx/log.htm?Start=hhmmddMMyy
Note: There is a limit to how much data can be displayed so if all data requested is not shown you will have to get the log again from when it
stopped previously. If logging digital outputs the log will show 0.0 for off and 1.0 for on.
Warning
Ensure that all power is
switched off before
installing or maintaining
this product
GMT0BST-1,M3.5.0/01:00:00,M10.5.0/02:00:00
allows you to change and set new parameters
allows you to put the parameters back to their original settings
Revision 2.6
Page 52 of 53
www.resourcedm.com

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pr0751-tdbPr0760-tdbPr0761-tdb

Table of Contents