I/O Objects & Properties; Analogue Input - Resource Data Management PR0750-TDB Installation & User Manual

Intuitive mercury tdb controller
Table of Contents

Advertisement

Intuitive Mercury 6-5M Controller with TDB
I/O Objects & Properties

Analogue Input

Icon
Properties
*Probe types: -
*If Probe type "Raw" is selected then no resistance to temperature conversion will take place, value displayed will be the probe's resistance
value in ohms.
Note: If input is left open circuit the block will give a very high reading i.e. 1999999. If the input is short circuited the block will give a very low
reading i.e. 7.3
Used in conjunction with an "In Range Block" this gives the equivalent feature of a digital input behaving like "Plant N/O and N/C"
**If an analog input has been configured to use a Custom profile then to select and use one of the preset probe types e.g. PT1000, the analog
input must be deleted and reinserted into the program.
Warning
Ensure that all power is
switched off before
installing or maintaining
this product
PT1000
2K
470R
700R
3K
2K25
100K
5K
6K
10K
10K Type 2 (USA)
Raw*
Custom**
Define
Fixed inputs are the Intuitive Mercury TDB Controller
built in Inputs.
Input:
Select the input from the drop-down menu.
If a probe has been selected, select the probe type*.
Revision 2.6
Page 21 of 53
www.resourcedm.com