Direct On/Off; Direct Pid; Reverse Pid - Resource Data Management PR0750-TDB Installation & User Manual

Intuitive mercury tdb controller
Table of Contents

Advertisement

Intuitive Mercury 6-5M Controller with TDB

Direct On/Off

B
C
D
Input A: Analogue input
Input B: Set Point
Input C: Diff above SP
Input D: Diff below SP

Direct PID

A
B
C
D
E
Input A: Analogue input
Input B: Set Point
Input C: Proportional constant
Input D: Integral
Input E: Derivative

Reverse PID

A
B
C
D
E
Input A: Analogue input
Input B: Set Point
Input C: Proportional constant
Input D: Integral
Input E: Derivative
Warning
Ensure that all power is
switched off before
installing or maintaining
this product
Icon
A
Icon
Icon
Diff above
Set Point
Diff below
Off
Output
Properties
This block performs a PID control
function where the set-point,
proportional, integral and derivative
values can be assigned.
The output will increase when the
analogue input is above setpoint, this
is normally used in cooling
applications
Properties
This block performs a PID control
function where the set-point,
proportional, integral and derivative
values can be assigned.
The output will decrease when the
analogue input is above setpoint, this
is normally used in heating
applications.
Revision 2.6
On
Page 39 of 53
www.resourcedm.com
Off