Power Requirements; General; Relay Specification; Specification - Resource Data Management PR0750-MOB Installation & User Manual

Mercury 2 & intuitive mercury mobile controller
Table of Contents

Advertisement

Mercury 2 & Intuitive Mobile Controller User Guide

Specification

Power requirements

Supply Voltage Range
Supply Frequency
Maximum supply current
Typical supply current

General

Operating temperature range
Storage temperature range
Environmental
Size
Approx Weight
Safety
EMC
Ventilation
Class 2 Insulation
Supply Fuse
Or MCB
Relay Fuse

Relay Specification

Relays 1-4 Mechanical Type (M)
Exclusive common
Max current
Max voltage
Relay Fuse
Relay 5 Mechanical Type (M)
Common connected to supply
live
Max current
Max voltage
Warning: Relay 5 output has hazardous voltages (Supply input voltage potential)
This does not apply to the Intuitive Mercury controller
Warning
Ensure that all power is
switched off before
installing or maintaining
this product
Please Note
Mercury Mk2 Controller
PR0710-MOB & PR0720-MOB
100 - 240 Vac ±10%
50 - 60 Hz
5.2 Amps (when relay 5 is fully loaded)
<1 Amp
0
0
+5
C to +50
C
0
0
-20
C to +65
C
Indoor use at altitudes up to 2000m, pollution
degree 1, installation category II. Voltage
fluctuations not to exceed ±10% of nominal
voltage.
78mm (W) x 36mm (H) x 110mm (D)
170 grams
EN61010
EN61326; 1997 +Amdt. A1; 1998
There is no requirement for forced cooling
ventilation
No protective Earth is required and none
should be fitted
The host equipment must provide a suitable
external over-current protection device such
as: -
Fuse: 6.3A 240 Vac Antisurge (T) HRC
conforming to IEC 60127
6A, 240 VAC Type C conforming to BS EN
60898
Not Fitted
6A Resistive (CosØ = 1)
2A Inductive ( CosØ = 0.4)
250Vac, 30V dc
N/A
3A (non inductive), COS=0.4 2A (inductive
load) 200,000 operations
250Vac (Internal supply)
For compliance with the LVD, relays 3, 4 and 5
commons must be at the same potential as the
supply voltage
Revision 1.1
Intuitive Mercury controller
PR0750-MOB & PR0760-MOB
100 - 240 Vac ±10%
50 - 60 Hz
2 Amps
<1 Amp
0
0
+5
C to +50
C
0
0
-20
C to +65
C
Indoor use at altitudes up to 2000m, pollution
degree 1, installation category II. Voltage
fluctuations not to exceed ±10% of nominal
voltage.
157mm (W) x 67mm (H) x 120 (D)
500 grams
EN61010
EN61326; 1997 +Amdt. A1; 1998
There is no requirement for forced cooling
ventilation
No protective Earth is required and none should
be fitted
Built in fuse holder, fuse 2A 240Vac Antisurge (T)
HRC conforming to IEC60127, 32 x 6.3mm
2A, 240 VAC Type C conforming to BS EN 60898
(Note: controller has integral 2A fuse)
10A 240Vac Antisurge (T) HRC conforming to
IEC60127, 32 x 6.3mm
10A Resistive (CosØ = 1)
3A Inductive ( CosØ = 0.4)
250Vac. 30V dc
10A 240Vac Antisurge (T) HRC conforming to
IEC60127, 32 x 6.3mm
Relay 5 Mechanical Type (M)
Exclusive common
10A Resistive (CosØ = 1)
3A Inductive ( CosØ = 0.4)
250Vac. 30V dc (external supply)
All relays are independent and can operate at
different potentials to the supply voltage.
!