Digital Edge Block; Analogue Edge Block; Reverse On/Off - Resource Data Management PR0750-TDB Installation & User Manual

Intuitive mercury tdb controller
Table of Contents

Advertisement

Intuitive Mercury 6-5M Controller with TDB

Digital Edge Block

Icon
Signal

Analogue Edge Block

Icon
Signal

Reverse On/Off

B
C
D
Input A: Analogue input
Input B: Set Point
Input C: Diff above SP
Input D: Diff below SP
Warning
Ensure that all power is
switched off before
installing or maintaining
this product
The block is used to detect the rising and falling edge of a digital signal.
Edge
Edge
Rising
Rising
The use of a SR-Latch on each output may be required.
Falling
Description
For any Rise on the Signal Input
Edge
The Edge and Rising Outputs will pulse high for 0.1 seconds
For any Falling Edge on the Signal Input
Rising
The Edge and Falling Outputs will pulse high for 0.1 seconds
The use of a SR-Latch on each output may be required.
Falling
Icon
A
On the rising edge of the input signal the "Edge" and "Rising" outputs will
pulse Hi for 0.1 seconds
On the falling edge of the signal input the Edge and Falling Outputs will
pulse Hi for 0.1 seconds
Diff above
Set Point
Diff below
On
Output
Revision 2.6