Intuitive Mercury TDB Controller

The Intuitive Mercury Controller with Data Builder is a versatile device intended for user programming. Some example applications are HVAC,
BMS and Refrigeration. The controller has 6 analogue probe inputs, which can also be used as volt free digital inputs, 5 relay outputs with on
board fusing as standard. In addition, the controller can also be specified with one or more solid state relays (SSRs) fitted. There are optional
daughter boards available which provide additional inputs and outputs, such as a high speed pulse counter. There is no intrinsic program, but all
of the inputs and outputs are available for use with either the on-board Data Builder program or a Data Manager Data Builder program to provide
the ultimate flexibility in control and monitoring applications.
The Intuitive Mercury TDB Controller requires an IP connection for uploading/ downloading TDB programmes to the controller. There is a
maximum of 2048 blocks available for use in a program, though this can be less depending on the type of blocks used. Up to 64 external Setting
Blocks are allowed in a program, if more than 64 Setting Blocks are used then the additional blocks will not appear in the controller webpage's or
on an RDM Data Manager. Any additional Setting Blocks used must be marked as "Internal".
There can be a total of 20 alarm Blocks and a total of 20 External I/O. If more than 20 I/O blocks are required they would have to be set as
internal.
Due to the flexibility of the TDB Editor it allows a user to create complex control strategies. RDM recommend that the developer of the TDB
application carry out functionality tests prior to installation to ensure the control strategy designed operates as expected e.g. all inputs can be
read, all outputs activate when operated by the TDB program and so forth. If the unit is to be connected to a Data Manager, RDM recommend
the developer also log on the controller to a Data Manager, for example to check the order of Inputs, Outputs and parameters.
Description
Intuitive Mercury 6-5M Controller with TDB application, integral display,
Intuitive Mercury 6-5M Controller with TDB application, remote display,

Configuration

The controller has no configuration until a Data Builder application has been developed and uploaded to the controller, see:

Compatible Network Interfaces

Intuitive Mercury controllers are capable of connecting to a TCP/IP local area network, or they can be used in standalone mode with no network
output. To connect to a network you must add the correct communications module. Connecting to any of these communication modules will
automatically be detected on power up and will affect the set up screens available to you.
The Intuitive Mercury 6-5 TDB Controller is supplied as standard with an internal RS232 network card, this allows connection to any of the above
external network interfaces. As alternatives, either an Ethernet interface or a WiFi network card is available. These can be supplied factory fitted
as an option or purchased separately as an interface kit.
Inputs & Outputs Descriptions
Note 1
A variety of probes can be used by the Data Builder Analogue block or a custom probe curve can be programmed. These inputs can
also be set to digital with a settable switching threshold (default 1000 ohms).
Note 2
See
Daughter Board

Compatible Remote Displays

When using the remote display variant of the controller the following displays are compatible.
Warning
Ensure that all power is
switched off before
installing or maintaining
this product

The Intuitive Mercury Range

From Resource Data Management
Description
IP Futura (Single Mercury to IP Interface)
Mercury IP Switch (IP support for 10 controllers)
Mercury IP Switch with Pressure/Humidity Inputs
Description
Intuitive Internal IP Network Card Interface Kit
Intuitive WiFi Network Card Interface kit (External Antenna)
Intuitive WiFi Network Card Interface kit (Internal Antenna)
Inputs / Outputs
Analogue/Digital Input 1-6
Relay 1-5
section for additional I/O.
Description
Mercury Mk2 Display
Humidistat Display
Description
Comments
Probe input
See note 1
N/O, N/C and Common
Volt Free
Part Number
PR0725
PR0445
Revision 2.6
Part Number
See
Ordering Information
See
Ordering Information
Getting started.
Part Number
PR0016
PR0018
PR0018-PHI
Part Number
PR0770
PR0769-EXT
PR0769-INT
Page 5 of 53