TARGETS MENU
Latched target message: No.
Description of problem: The
programmed.
How often the test is performed: On power up and whenever the
setting is altered
What to do: Program all settings and then set
MODULE FAILURE___:
Contact Factory (xxx)
Latched target message: Yes.
Description of problem: Module hardware failure detected. Module Failures 1 to 11 are major. The system can reboot
for four of these, as follows.
MODULE FAILURE 06 — Event message reads SYSTEM INTEGRITRY RECOVERY 06 when a reboot was required and
otherwise MODULE FAILURE 06 when a failure was detected
MODULE FAILURE 07 — Event message reads SYSTEM INTEGRITRY RECOVERY 07 when a reboot was required and
otherwise MODULE FAILURE 07 when a failure was detected
MODULE FAILURE 08 — Event message reads SYSTEM INTEGRITRY RECOVERY 08 when a reboot was required and
otherwise MODULE FAILURE 08 when a failure was detected
MODULE FAILURE 11 — Event message reads SYSTEM INTEGRITRY RECOVERY 11 when a reboot was required and
otherwise MODULE FAILURE 11 when a failure was detected
How often the test is performed: Module dependent.
What to do: Contact the factory and supply the failure code noted in the display. The "xxx" text identifies the failed
module (for example, F8L).
7.2.2.3 Minor self-test error messages
Most of the minor self-test errors can be disabled. See the settings in the User-programmable Self-tests section in chapter
5.
MODULE FAILURE___:
Contact Factory (xxx)
Latched target message: Yes.
Description of problem: Module hardware failure detected. Module Failures 12 and 31 to 33 are minor.
7
How often the test is performed: Module dependent.
What to do: Contact the factory and supply the failure code noted in the display. The "xxx" text identifies the failed
module (for example, F8L).
For Module Failure 31, a new process card hardware is available. The process card hardware has been enhanced to
support new features, such as fast distance protection, Synchrophasors Frequency, and Rate of Change of Frequency
calculations to conform to C37.118 - 2005 standard. The new functionality leveraging the hardware is supported with
firmware revision 7.25 and above. When using an older revision of the process card with a new firmware revision
(7.25), Module Failure 31 indicates the limited functionality. If your application requires the new functionality, then new
process card hardware is required and otherwise you can continue using the existing hardware. To know the revision
of your hardware, contact the factory.
MAINTENANCE ALERT:
Replace Battery
Latched target message: Yes.
Description of problem: The battery is weak or not functioning. It powers the real time clock. This message displays as
Battery Fail in the event records. When the battery weakness reaches a critical level, the message displays persistently
on the front panel and no front panel key navigation is possible.
7-6
PRODUCT SETUP  INSTALLATION  RELAY SETTINGS
.
PRODUCT SETUP  INSTALLATION  RELAY SETTINGS
PRODUCT SETUP  INSTALLATION  RELAY SETTINGS
B90 LOW IMPEDANCE BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
CHAPTER 7: COMMANDS AND TARGETS
setting indicates the B90 is not
to "Programmed."