CHAPTER 5: SETTINGS
Clearing records with user-programmable operands is not protected by the command password. However, user-
programmable pushbuttons are protected by the command password. Thus, if they are used to clear records, the user-
programmable pushbuttons can provide extra security if required.
For example, to assign user-programmable pushbutton 1 to clear demand records, apply the following settings.
1.
Assign the clear demand function to pushbutton 1 by making the following change in the
 CLEAR RELAY RECORDS
: "
CLEAR DEMAND
PUSHBUTTON 1 ON
2.
Set the properties for user-programmable pushbutton 1 by making the following changes in the
SETUP  USER-PROGRAMMABLE PUSHBUTTONS  USER PUSHBUTTON 1
PUSHBUTTON 1 FUNCTION
PUSHBTN 1 DROP-OUT TIME

5.3.5 Communications

5.3.5.1 Menu
SETTINGS  PRODUCT SETUP  COMMUNICATIONS
 COMMUNICATIONS
5.3.5.2 Serial ports
SETTINGS  PRODUCT SETUP  COMMUNICATIONS  SERIAL PORTS
 SERIAL PORTS
B90 LOW IMPEDANCE BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
menu:
"
: "Self-reset"
: "0.20 s"
 SERIAL PORTS
 NETWORK
 IPv4 ROUTE TABLE
 MODBUS PROTOCOL
 PROTOCOL
 DNP PROTOCOL
 DNP / IEC104
 POINT LISTS
 IEC 61850 PROTOCOL
 WEB SERVER
 HTTP PROTOCOL
 TFTP PROTOCOL
 IEC 60870-5-104
 PROTOCOL
 IEC103
 PROTOCOL
RS232 BAUD
RATE: 115200
RS485 COM2 BAUD
RATE: 19200
SETTINGS  PRODUCT SETUP
SETTINGS  PRODUCT
menu:
See page 5-25
See page 5-28
See page 5-31
See page 5-34
See page 5-34
See page 5-35
See page 5-39
Access in EnerVista
See page 5-40
See page 5-78
See page 5-79
See page 5-79
See page 5-81
Range: 19200, 115200
Range: 300, 1200, 2400, 4800, 9600, 14400, 19200,
28800, 33600, 38400, 57600, 115200 bit/s
PRODUCT SETUP