GE B90 Instruction Manual page 309

Low impedance bus differential system
Hide thumbs Also See for B90:
Table of Contents

Advertisement

CHAPTER 5: SETTINGS
Table 5-21: Overcurrent curve types
IEEE
IEEE Extremely Inverse
IEEE Very Inverse
IEEE Moderately Inverse
A time dial multiplier setting allows selection of a multiple of the base curve shape (where the time dial multiplier = 1) with
the curve shape (
) setting. Unlike the electromechanical time dial equivalent, operate times are directly proportional
CURVE
to the time multiplier (
TD MULTIPLIER
or base curve values. Setting the multiplier to zero results in an instantaneous response to all current levels above pickup.
Time overcurrent time calculations are made with an internal energy capacity memory variable. When this variable
indicates that the energy capacity has reached 100%, a time overcurrent element operates. If less than 100% energy
capacity is accumulated in this variable and the current falls below the dropout threshold of 97 to 98% of the pickup value,
the variable must be reduced. Two methods of this resetting operation are available: "Instantaneous" and "Timed." The
"Instantaneous" selection is intended for applications with other relays, such as most static relays, which set the energy
capacity directly to zero when the current falls below the reset threshold. The "Timed" selection can be used where the
relay must coordinate with electromechanical relays.
IEEE curves
The IEEE time overcurrent curve shapes conform to industry standards and the IEEE C37.112-1996 curve classifications for
extremely, very, and moderately inverse curves. The IEEE curves are derived from the operate and reset time equations.
where
T = operate time (in seconds)
TDM = Multiplier setting
I = input current
I
= Pickup Current setting
pickup
A, B, p = constants defined in the table
T
= reset time in seconds (assuming energy capacity is 100% and RESET is "Timed")
RESET
t
= characteristic constant defined in the table
r
Table 5-22: IEEE inverse time curve constants
IEEE curve shape
IEEE Extremely Inverse
IEEE Very Inverse
IEEE Moderately Inverse
Table 5-23: IEEE curve trip times (in seconds)
Multiplier
Current ( I / I
pickup
(TDM)
1.5
2.0
IEEE Extremely Inverse
0.5
11.341
4.761
1.0
22.682
9.522
2.0
45.363
19.043
4.0
90.727
38.087
B90 LOW IMPEDANCE BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
IEC
IEC Curve A (BS142)
IEC Curve B (BS142)
IEC Curve C (BS142)
IEC Short Inverse
) setting value. For example, all times for a multiplier of 10 are 10 times the multiplier 1
A
B
28.2
0.1217
19.61
0.491
0.0515
0.1140
)
3.0
4.0
5.0
1.823
1.001
0.648
3.647
2.002
1.297
7.293
4.003
2.593
14.587
8.007
5.187
GE type IAC
IAC Extremely Inverse
IAC Very Inverse
IAC Inverse
IAC Short Inverse
p
t
r
2.0000
29.1
2.0000
21.6
0.02000
4.85
6.0
7.0
8.0
0.464
0.355
0.285
0.927
0.709
0.569
1.855
1.418
1.139
3.710
2.837
2.277
GROUPED ELEMENTS
Other
2
I
t
Definite Time
Eq. 5-5
9.0
10.0
0.237
0.203
0.474
0.407
0.948
0.813
1.897
1.626
5-153
5