CHAPTER 5: SETTINGS
The Time Overcurrent (TOC) element is provided for backup protection with a choice of inverse time curves. The element is
enabled only when
PRODUCT SETUP  B90 FUNCTION  B90 FUNCTION
each CT input.

5.6.7 End fault protection

SETTINGS  GROUPED ELEMENTS  SETTING GROUP 1(6)  END FAULT PROTECTION 1(24)
 END FAULT
 PROTECTION 1
B90 LOW IMPEDANCE BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
TOC1 TD MULTIPLIER:
1.00
TOC1 RESET:
Instantaneous
TOC1 BLOCK:
Off
TOC1 TARGET:
Self-Reset
TOC1 EVENTS:
Disabled
Figure 5-82: Time overcurrent logic
EFP1 FUNCTION:
Disabled
EFP1 CT:
F1
EFP1 PICKUP:
1.200 pu
EFP1 BREAKER OPEN:
Off
EFP1 BKR DELAY:
0.400 s
EFP1 MANUAL CLOSE:
Off
EFP1 PICKUP DELAY:
0.040 s
Range: 0.00 to 600.00 in steps of 1
Range: Instantaneous, Timed
Range: FlexLogic operand
Range: Self-Reset, Latched, Disabled
Range: Disabled, Enabled
is set to "Protection". One TOC element is available per
Range: Disabled, Enabled
Range: Available current channels
Range: 0.020 to 30.000 pu in steps of 0.001
Range: FlexLogic operand
Range: 0.000 to 65.535 s in steps of 0.001
Range: FlexLogic operand
Range: 0.000 to 65.535 s in steps of 0.001
GROUPED ELEMENTS
5
5-159