PRODUCT SETUP
The user-programmable LED settings select the FlexLogic operands that control the LEDs. If the
Reset" (the default setting), the LED illumination tracks the state of the selected LED operand. If the
"Latched," the LED, once lit, remains so until reset by the faceplate
communications channel, or from any programmed operand, even if the LED operand state de-asserts.
Table 5-14: Recommended settings for user-programmable LEDs
Setting
LED 1 operand
LED 2 operand
LED 3 operand
LED 4 operand
LED 5 operand
LED 6 operand
LED 7 operand
LED 8 operand
LED 9 operand
LED 10 operand
LED 11 operand
LED 12 operand

5.3.11 User-programmable self-tests

5
SETTINGS  PRODUCT SETUP  USER-PROGRAMMALBE SELF TESTS
 USER-PROGRAMMABLE
 SELF TESTS
All major self-test alarms are reported automatically with their corresponding FlexLogic operands, events, and targets.
Most of the minor alarms can be disabled if so wanted.
5-96
Parameter
SETTING GROUP ACT 1
SETTING GROUP ACT 2
SETTING GROUP ACT 3
SETTING GROUP ACT 4
SETTING GROUP ACT 5
SETTING GROUP ACT 6
Off
Off
Off
Off
Off
Off
DIRECT RING BREAK
FUNCTION: Enabled
DIRECT DEVICE OFF
FUNCTION: Enabled
RxGOOSE OFF
FUNCTION: Enabled
FIRST ETHERNET FAIL
FUNCTION: Disabled
SEC. ETHERNET FAIL
FUNCTION: Disabled
THIRD ETHERNET FAIL
FUNCTION: Disabled
SFP MODULE FAIL
FUNCTION: Disabled
BATTERY FAIL
FUNCTION: Enabled
SNTP FAIL
FUNCTION: Enabled
IRIG-B FAIL
FUNCTION: Enabled
PTP FAIL
FUNCTION: Enabled
button, from a remote device via a
RESET
Setting
Parameter
LED 13 operand
Off
LED 14 operand
Off
LED 15 operand
Off
LED 16 operand
Off
LED 17 operand
Off
LED 18 operand
Off
LED 19 operand
Off
LED 20 operand
Off
LED 21 operand
Off
LED 22 operand
Off
LED 23 operand
Off
LED 24 operand
Off
Range: Disabled, Enabled. Valid for units equipped
with Direct Input/Output module.
Range: Disabled, Enabled. Valid for units equipped
with Direct Input/Output module.
Range: Disabled, Enabled
Range: Disabled, Enabled
Range: Disabled, Enabled
Range: Disabled, Enabled
Range: Disabled, Enabled
Range: Disabled, Enabled
Range: Disabled, Enabled
Range: Disabled, Enabled
Range: Disabled, Enabled
B90 LOW IMPEDANCE BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS
setting is "Self-
LED 1 TYPE
setting is
LED 1 TYPE