CHAPTER 5: SETTINGS
GROUPED ELEMENTS
— This setting is used to set the phase current fault detection level. Generally this setting detects the
BF1 AMP LOSET PICKUP
lowest expected fault current on the protected breaker, after a breaker opening resistor is inserted approximately 90% of
resistor current).
Figure 5-76: Breaker failure current supervision logic
5
B90 LOW IMPEDANCE BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
5-147