Indication Of Faults - Siemens RVA63.280 Basic Documentation

Boiler and heating circuit controllers
Table of Contents

Advertisement

Benefit
Description
Setting
Effect
Note
Fault messages
Device faults
Siemens Building Technologies
Landis & Staefa Division
1.30

Indication of faults

Straightforward checking of plant.
Fault tracing is made easier.
The controller indicates faults that may have occurred in the controller itself or in the
system.
In normal operation, the display shows "Er" if a fault has occurred
Display
0...255
The first entry in the fault list will automatically be displayed on this line.
By pressing
, it is possible to switch between fault messages.
The controller can store a maximum of 2 fault messages. The faults message will be
cleared only after the cause of the fault has been removed. If additional faults are
present, they will be stored as soon as storage capacity becomes available.
Faults that can occur on the controller:
Display
Description of fault
Blank
No fault
10
Outside sensor
20
Boiler sensor
28
Flue gas temperature sensor
30
Flow temperature sensor 1
32
Flow temperature sensor 2
50
D.h.w. temperature sensor connected to B3
52
D.h.w. temperature sensor connected to B31
58
D.h.w. thermostat
61
Fault room unit (A6)
62
Wrong room unit (A6)
66
Fault room unit 2 (A7)
67
Wrong room unit 2 (A7)
80
No LPB communication
81
Short-circuit LPB
82
Address collision on LPB (same address several times)
86
Short-circuit PPS (A6)
87
Short-circuit PPS (A7)
100
2 clock masters present
140
Inadmissible LPB device or segment number
146
Inadmissible plant configuration
150
General BMU fault
162
Fault contact H2
Basic Dokumentation RVA63.280, RVA53.280
Unit
-
65/184
CE1P2374E
19.04.2001