Siemens Building Technologies
Landis & Staefa Division
3.10

Control of boiler pump

Boiler pump control mode can be selected.
The setting defines the criteria according to which the boiler pump shall be operated.
Setting range
0 / 1
The settings have the following meaning:
0
The boiler pump operates when there is a demand for heat.
In that case, the boiler pump responds to locking signals.
1
The boiler pump operates when there is a demand for heat or when the burner
operates. In that case, the boiler pump does not respond to locking signals
(protective boiler start-up).
Basic Dokumentation RVA63.280, RVA53.280
Unit
-
Factory setting
0
141/184