Maximum Limitation Of Flow Temperature Setpoint (Tvmax) - Siemens RVA63.280 Basic Documentation

Boiler and heating circuit controllers
Table of Contents

Advertisement

Benefit
Description
Setting
Effect
Important
Limitation
90/184
Siemens Building Technologies
Landis & Staefa Division
2.29
Maximum limitation of flow temperature
setpoint (TVmax)
Prevents too high flow temperatures.
Minimum and maximum limitation define the range within which the flow temperature
setpoint may vary.
Setting range
TVmin...95
Tvmin Minimum limitation of flow temperature setpoint (setting on line 105)
The setting will ensure that the flow temperature setpoint will not exceed a maximum
level.
Maximum limitation is not to be regarded as a safety function as required with
underfloor heating systems, for example.
TV
max
akt
min
0
10
20
30
TVw
Current flow temperature setpoint
105
Minimum limitation of flow temperature setpoint
107
Maximum limitation of flow temperature setpoint
If the flow temperature setpoint demanded by the heating circuit reaches the maximum
limit and the outside temperature falls, the flow temperature setpoint will be maintained
at that limit, in other words, it will not be allowed to exceed it.
Basic Dokumentation RVA63.280, RVA53.280
Unit
°C
TVw
40
50
60
70
Factory setting
80
°C
80
90
100
CE1P2374E
19.04.2001