Setpoints; Display Of Boiler Temperature Setpoint; Display Of Common Flow Temperature Setpoint - Siemens RVA63.280 Basic Documentation

Boiler and heating circuit controllers
Table of Contents

Advertisement

Benefits
Description
Setting
Benefits
Description
Setting
74/184
Siemens Building Technologies
Landis & Staefa Division

Setpoints

2.13

Display of boiler temperature setpoint

Indication of boiler temperature setpoint.
Better overview of the plant's operating state.
The current boiler temperature setpoint will automatically be displayed on this line.
Display
0...140
The setpoint can only be displayed, but not changed. The function helps better
understand the control sequences taking place in the controller.
No setpoint is displayed (---) when there is no heat demand from the consumers.
2.14
Display of common flow temperature
setpoint

Display of common flow temperature setpoint.

Better overview of the plant's operating state.
The current common flow temperature setpoint will automatically be displayed on this
line.
Display
0...140
The setpoint can only be displayed, but not changed. The function helps better
understand the control sequences taking place in the controller.
No setpoint is displayed (---) when there is no heat demand from the consumers.
Basic Dokumentation RVA63.280, RVA53.280
Unit
°C
Unit
°C
CE1P2374E
19.04.2001