Direction Of Rotation; Reset; Operational Status Indication By Led On The Actuator - Siemens LMV51 Series Basic Documentation

Burner control with integrated fuel / air ratio control and load control for forced-draft burners
Hide thumbs Also See for LMV51 Series:
Table of Contents

Advertisement

Direction of rotation

Reset

Operational status indication
by LED on the actuator
Power is fed to
unaddressed actuator
Button for addressing is
pressed (display during
addressing procedure)
Addressing completed,
normal operation of actuator
92/157
Siemens Building Technologies
HVAC Products
To select the direction of rotation, choose the following menu on the AZL51...:
«Params & Display» ® «Actuators» ® «DirectionRot»
You are given the choice of «Standard» and «Reversed»:
Standard
90°
When facing the end of the drive shaft
The parameter is filed in the basic unit so that the direction of rotation need not be
reentered when replacing the actuator.
This facility makes it possible to reset an already addressed actuator in the case of a
replacement, repair, or if addressing is wrong (wrong address assignment by the user).
For that purpose, the user must press the actuator's addressing button for at least 10
seconds when the actuator is in normal operation. The actuator will then reset its
address which is indicated by the LED when steady on.
LED steady ON
ON
OFF
The actuator gives the addressing number via the LED. The blink interval is 200
ms:
1 pulse
Þ
Þ
2 pulses
Þ
3 pulses
4 pulses
Þ
After each blink cycle, there is a pause of 1.2 seconds.
Example of an actuator for gas
ON
OFF
Basic Documentation LMV51...
6 Display and operating unit AZL51...
(not mounted)
air actuator
gas actuator
oil actuator
auxiliary actuator
Reversed
90°
7550d29E/0502
7550d11E
Time
7550d12E
Time
CC1P7550en
29.05.2002

Advertisement