2.48
Range of action of central changeover
The range of action of central changeover can be defined.
Function for defining the range of action of central changeover.
Setting range
0 / 1
The range of action can be defined for central changeover "Changeover of operating
mode" (HCs + d.h.w., HCs), "Summer / winter changeover" and "Stand-by". The range
of action can be defined by making the following settings:
0
Changeover takes place with all controllers in the same segment.
1
Changeover takes place with all controllers in the entire system (LPB).
The setting is of importance only if the controller is defined as the master and located in
segment 0 (address 0/1). With any other addressing, it has no effect.
Basic Dokumentation RVA63.280, RVA53.280