D.h.w. push

Availability of d.h.w. is also ensured during non-occupancy times.
If, due to unexpected demand, the d.h.w. storage tank is emptied, the d.h.w. push
provides one-time charging of the storage tank until the nominal d.h.w. temperature
setpoint is reached.
The d.h.w. push is triggered as soon as the actual d.h.w. temperature falls below the
reduced d.h.w. setpoint (line 51
differential (line 120).
TBWx < TBWR - 2 SDBw
When the d.h.w. push is triggered, the storage tank is charged once until the nominal
d.h.w. temperature setpoint (line 120) is reached.
Then, normal operation according to the d.h.w. heating program is resumed.
TBWw
SDBW
TBWR
TBWw
TBWR
SDBW Switching differential d.h.w.
TBWw Nominal setpoint of the d.h.w. temperature
TBWR Reduced setpoint of the d.h.w. temperature
Basic Dokumentation RVA63.280, RVA53.280
) by an amount that exceeds twice the switching
OEM
TBWx
Push
SDBW
·
2
SDBW
t
t
CE1P2374E
19.04.2001