Siemens Building Technologies
Landis & Staefa Division
2.7
Actual value 1 of d.h.w. temperature
(TBWx)
The higher d.h.w. temperature acquired with the d.h.w. sensor will automatically be
displayed on this line.
Display
0...140
If only one d.h.w. temperature sensor is connected, lines 61 and 62 will show the same
value.
2.8

Actual value 2 of d.h.w. temperature

The lower d.h.w. temperature acquired with the d.h.w. temperature sensor will
automatically be displayed on this line.
Display
0...140
If only one d.h.w. sensor is connected, lines 61 and 62 will show the same value
For information about d.h.w. heating with 2 temperature sensors, refer to section "Input
B31/H2"
2.9
Display of maximum flue gas temperature
(TGxmax)
This display shows the highest flue gas temperature acquired since the last reset.
Display
0...350
Using the + / - buttons, the display can be reset to the current value. For that purpose,
both buttons must be pressed together for 3 seconds. The value is reset as soon as the
display stops flashing.
In the event of an open-circuit or short-circuit of the sensor, the display maintains the
maximum temperature value last measured. This value can be reset after rectification
of the fault.
Basic Dokumentation RVA63.280, RVA53.280
Unit
°C
Unit
°C
Unit
°C
71/184
CE1P2374E
19.04.2001