Heating Circuit; Parallel Displacement Of Heating Curve - Siemens RVA63.280 Basic Documentation

Boiler and heating circuit controllers
Table of Contents

Advertisement

Benefit
Description
Setting
Effect
Example
Parallel displacement
Siemens Building Technologies
Landis & Staefa Division

Heating circuit

2.23

Parallel displacement of heating curve

Readjustment of room temperature setting, especially in plants without room sensor.
Produces a parallel displacement of the heating curve in order to achieve a better
match of heat generation and heat consumption.
Setting range
-4.5...+4.5
By changing the value entered, all room temperature setpoints will be appropriately
raised or lowered. This allows the room temperature setpoints to be matched to the
effective room temperatures.
If a nominal room temperature setpoint of 20 °C adjusted on the controller always
produces a room temperature of 22 °C, displace the heating curve downward by 2 °C.
Each setpoint readjustment, be it via the setting value or the operational level, is a
parallel displacement of the heating curve.
TV
°C
100
90
80
70
60
50
40
30
30
20
10
0
TV
Flow temperature
TA
Composite outside temperature
TRw
Room temperature setpoint
Basic Dokumentation RVA63.280, RVA53.280
Unit
°C (K)
10
0
-10
10
0
Factory setting
0.0
-20
°C
-30
83/184
CE1P2374E
19.04.2001
TA

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rva53.280

Table of Contents