Activating The Function; Function; Display; Aborting The Function - Siemens RVA63.280 Basic Documentation

Boiler and heating circuit controllers
Table of Contents

Advertisement

Temperature profile
Particularities
Siemens Building Technologies
Landis & Staefa Division
2.35.2

Activating the function

If setting 1), 2) or 3) is made via the setting parameter, the respective floor curing
function will be carried out.
The floor curing function can be activated only with applications using a mixing heating
circuit.
With the pump heating circuit application, this function cannot be activated.
2.35.3

Function

When the floor curing function is activated, parameter "Maximum limitation of floor
temperature Tvmax" will automatically be set to 55 °C. This value will then be used as
the maximum value for the floor curing function and will be maintained when the floor
curing function is terminated.
The starting day, that is, the period of time from activation until midnight, is not
considered day 1 of the selected temperature profile. The starting day is called day 0
and adopts the flow temperature value of day 1.
The flow temperature changes dictated by the temperature profile always take place at
midnight.
When the floor curing function is activated, the mixing valve ensures that the flow
temperature dictated by the temperature profile will be maintained. This means that
protective boiler start-up or d.h.w. heating with absolute or shifting priority have no
impact on the floor curing function.
In the event of a power failure, the function will be resumed where operation was
stopped.
Manual operation is given priority over the floor curing function. When manual operation
is activated, the mixing valve will be de-energized (relay contacts open). As a result, the
floor curing function does not affect the mixing valve.
2.35.4

Display

When the floor curing function is activated, the LED of the current heating circuit
operating mode flashes.
2.35.5

Aborting the function

The following events cause abortion of the floor curing function:
The selected floor curing function is completed.
Setting parameter "Floor curing function" is set to active.
Basic Dokumentation RVA63.280, RVA53.280
99/184
CE1P2374E
19.04.2001

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rva53.280

Table of Contents