Reference room
Siemens Building Technologies
Landis & Staefa Division
2.27

Room unit values

This setting offers the possibility of assigning the action of the room unit values to one
of the heating circuits.
Assignment of the transmitted room unit values to one of the two heating circuits:
Heating circuit values are:
Actual value
Actual value of the room temperature
Room unit operating modes can be assigned in the same way, using setting line 103.
Setting range
0...2
The room unit values affect the selected heating circuits, depending on the setting
made.
Entry:
0
Room unit 1 (A6)
Room unit 2 (A7)
The room unit values affect exclusively the respective heating circuit (parallel).
1
Room unit 1 (A6)
Room unit 2 (A7)
The room unit values affect exclusively the other heating circuit (crossed).
2
Room unit 1 (A6)
Room unit 2 (A7)
The values of room unit 1 affect heating circuits 1 and 2.
It should be considered that the room in which the room unit is installed also is the
reference room for the room temperature influence.
Basic Dokumentation RVA63.280, RVA53.280
Unit
-
acting on heating circuit 1
acting on heating circuit 2
acting on heating circuit 2
acting on heating circuit 1
acting on heating circuits 1 and 2
with no action
Factory setting
0
87/184
CE1P2374E
19.04.2001