Section 3: Configuration
November 2012
AMS device manager
Right click on the device and select Diagnostics and Test, then Loop Test from the menu.
1.
2.
3.
4.
5.
a.
b. If the values do not match, the meter may be attached to the wrong loop, there may be
After completing the test procedure, the display returns to the Loop Test screen to choose
another output value or to end loop testing.
6.
7.
8.
3.13

Advanced functions

3.13.1
Saving, recalling, and cloning configuration data
Use the cloning feature of the Field Communicator or the AMS Device Manager "User
Configuration" feature to configure several 3051 transmitters similarly. Cloning involves
configuring a transmitter, saving the configuration data, then sending a copy of the data to a
separate transmitter. Several possible procedures exist when saving, recalling, and cloning
configuration data. For complete instructions refer to the Field Communicator manual
(publication no. 00809-0100-4276) or AMS Device Manager on-line guides. One common
method is as follows:
64
a. For 4-20 mA HART output, connect a reference meter to the transmitter by either
connecting the meter to the test terminals on the terminal block, or shunting
transmitter power through the meter at some point in the loop.
b. For 1-5 Vdc Low Power HART output, connect a reference meter to the V
Click Next after setting the control loop to manual.
Select desired analog output level. Click Next.
Click Next to acknowledge output being set to desired level.
Check that the reference meter displays the commanded output value.
If the values match, the transmitter and the loop are configured and functioning
properly.
a fault in the wiring or power supply, the transmitter may require an output trim, or the
reference meter may be malfunctioning.
Select End and click Next to end loop testing.
Select Next to acknowledge the loop can be returned to automatic control.
Select Finish to acknowledge the method is complete.
Reference Manual
00809-0100-4001, Rev JA
terminal.